DEN-5674: Added alarm sub-rank property and use for determining top priority alarm for UI.

  1. … 1 more file in changeset.
DEN-5674: Added synchronize of alarm audio/lamp control with published alarm state so that UI can flash alarm in sync w/ lamp. Added alarm audio.

  1. … 2 more files in changeset.
DEN-5674: Updated alarm messaging. Added concept of alarm condition detected and ability to clear this. Clear all recoverable alarms when user chooses an action.

DEN-5887: Fixed name format for const data to all caps w/ underlines per coding standard.

  1. … 5 more files in changeset.
DEN-5887: Added controller type property to PI controller as was added in DG stack. Added max I step size to prevent lasting effects of a large but brief disturbance in control input.

DEN-5887: Moved some load cell functions from dialysate outlet pump controller to DG Interface module. Added small and large moving average filters to load cell readings. Use small moving average for normal UF tracking/control and use large moving average for baseline and final reservoir weights to minimize reservoir transition errors due to load cell noise.

  1. … 6 more files in changeset.
DEN-5381: Removed test support macros

  1. … 9 more files in changeset.
DEN-4641: Addressed code review feedback.

  1. … 5 more files in changeset.
DEN-4641: Merged with master. Fixed merge conflicts. Addressed code review feedback.

  1. … 19 more files in changeset.
DEN-4641: Added new alarm IDs to alarm table.

DEN-4641: Updates to IT.

  1. … 1 more file in changeset.
DEN-4641: Updates to UT.

DEN-5754: Created common enum for saline bolus and heparin commands.

DEN-4641: Updated alarm list with new alarm.

DEN-4641: Distributed remaining payload record definitions to associated modules and deleted MessagePayloads.h. Added messaging and verification of in-line pressure limit changes.

  1. … 10 more files in changeset.
DEN-4640: Added inline pressure alarm checks.

  1. … 1 more file in changeset.
DEN-4641: Added new alarm IDs to alarm table. Added support for new Dialin commands to get, erase HD calibration data.

Fixed merge conflict - missing new alarm IDs.

Fixed merge conflict from common.

Fixed merge conflicts from master. Fixed some dev testing issues from merge.

  1. … 21 more files in changeset.
DEN-4641: Added support for Dialin request of calibration data.

DEN-4641: Changed HD pump Dialin set point override commands to simply set commands.

  1. … 6 more files in changeset.
DEN-4641: Removed last change allowing op mode restore from fault mode.

  1. … 2 more files in changeset.
DEN-4641: More fixes to HD pump motor speed measurement. Dialin cmd to clear all alarms will also restore op mode to prior if in fault mode.

  1. … 5 more files in changeset.
DEN-4641: Minor fixes to pump speed measurement and Dialin alarm features per verification.

  1. … 3 more files in changeset.
DEN-4641: Calculate HD pump motor speed more frequently. Added support for Dialin command to clear all alarms.

  1. … 5 more files in changeset.
DEN-4817: Changed alarms' behaviors

DEN-4640: Updated HD pump alarm properties per SRS.

DEN-4640: clear pump direction error counter if not in control state.

  1. … 3 more files in changeset.
DEN-4640: Addressed code review comments.

  1. … 3 more files in changeset.