Index: firmware/App/Controllers/DialInFlow.c =================================================================== diff -u -r4add9605a250a0b953217c8673204b705128561b -ra053cecf0673654e2bc03e9a34ff15845c8cff93 --- firmware/App/Controllers/DialInFlow.c (.../DialInFlow.c) (revision 4add9605a250a0b953217c8673204b705128561b) +++ firmware/App/Controllers/DialInFlow.c (.../DialInFlow.c) (revision a053cecf0673654e2bc03e9a34ff15845c8cff93) @@ -75,6 +75,7 @@ /// Persist time (task intervals) for flow vs. motor speed error condition. static const U32 DIP_FLOW_VS_SPEED_PERSIST = ((5 * MS_PER_SECOND) / TASK_PRIORITY_INTERVAL); +//static const U32 DIP_FLOW_VS_SPEED_PERSIST = ((60 * MS_PER_SECOND) / TASK_PRIORITY_INTERVAL); //DN-03NOV2022 - Make it 1 minutes for testing /// Persist time (task intervals) for motor off error condition. static const U32 DIP_OFF_ERROR_PERSIST = ((5 * MS_PER_SECOND) / TASK_PRIORITY_INTERVAL); /// Persist time (task intervals) motor speed error condition.