Index: firmware/App/Controllers/ConductivitySensors.c =================================================================== diff -u -r5e3a46112ebab361a33b9f7cadb619eb12b44c0f -r35179cc5895f6b7b9b1f8338754836898514a14e --- firmware/App/Controllers/ConductivitySensors.c (.../ConductivitySensors.c) (revision 5e3a46112ebab361a33b9f7cadb619eb12b44c0f) +++ firmware/App/Controllers/ConductivitySensors.c (.../ConductivitySensors.c) (revision 35179cc5895f6b7b9b1f8338754836898514a14e) @@ -57,6 +57,7 @@ #define MAX_CONDUCTIVITY_SENSOR_FAILURE_WINDOW_MS ( 60 * MS_PER_SECOND ) ///< Conductivity sensor error window. #define RO_REJECTION_RATIO_OUT_OF_RANGE_VALUE 1.0F ///< Out of range value for RO rejection ratio when CPi conductivity is zero. + #define MAX_RO_REJECTION_RATIO_ALLOW 0.10F ///< Maximum RO rejection ratio. #define MAX_CPO_CONDUCTIVITY_ALLOW 30.0F ///< Maximum CPo sensor conductivity value. @@ -289,11 +290,9 @@ /*********************************************************************//** * @brief * The checkInletWaterConductivity function checks inlet water conductivity value - * and triggers an alarm when conductivity value is not within the specified - * values. + * and triggers an alarm when conductivity value is out of allowed range. * @details Inputs: CPi sensor conductivity - * @details Outputs: Trigger warning alarm if conductivity is in the warning - * range. Trigger alarm if conductivity is below minimum conductivity. + * @details Outputs: Trigger alarms when conductivity is out of allowed range * @return none *************************************************************************/ void checkInletWaterConductivity( void )