Index: firmware/App/Controllers/ConductivitySensors.c =================================================================== diff -u -r750a8b61a1e9a63823ecc6ed441cd01524ffc02b -r95eefee71702fbf031025dc35ebaf553dfb050b7 --- firmware/App/Controllers/ConductivitySensors.c (.../ConductivitySensors.c) (revision 750a8b61a1e9a63823ecc6ed441cd01524ffc02b) +++ firmware/App/Controllers/ConductivitySensors.c (.../ConductivitySensors.c) (revision 95eefee71702fbf031025dc35ebaf553dfb050b7) @@ -238,18 +238,17 @@ /*********************************************************************//** * @brief - * The isInletWaterConductivityInRange function checks inlet water conductivity value + * The checkInletWaterConductivity function checks inlet water conductivity value * and triggers an alarm when conductivity value is not within the specified * values. * @details Inputs: CPi sensor conductivity * @details Outputs: Trigger warning alarm if conductivity is in the warning * range. Trigger alarm if conductivity is below minimum conductivity. - * @return TRUE if the inlet water conductivity is in range otherwise, FALSE + * @return none *************************************************************************/ -BOOL isInletWaterConductivityInRange( void ) +void checkInletWaterConductivity( void ) { #ifndef DISABLE_WATER_QUALITY_CHECK - BOOL status = TRUE; F32 conductivity = getConductivityValue( CONDUCTIVITYSENSORS_CPI_SENSOR ); BOOL isConductTooLow = ( conductivity < MAX_COND_SENSOR_CPI_WARNING_LOW ? TRUE : FALSE ); BOOL isConductInWarningRange = ( conductivity > MAX_COND_SENSOR_CPI_WARNING_HIGH ? TRUE : FALSE ); @@ -273,14 +272,6 @@ { checkPersistentAlarm( ALARM_ID_INLET_WATER_CONDUCTIVITY_IN_HIGH_RANGE, FALSE, conductivity, MAX_COND_SENSOR_CPI_WARNING_HIGH ); } - - if ( ( TRUE == isAlarmActive( ALARM_ID_INLET_WATER_CONDUCTIVITY_IN_LOW_RANGE ) ) || - ( TRUE == isAlarmActive( ALARM_ID_INLET_WATER_CONDUCTIVITY_IN_HIGH_RANGE ) ) ) - { - status = FALSE; - } - - return status; #endif }