Index: vectorcast/Hercules_RM46_HD_Project/environment/VOLTAGES/VOLTAGES.tst =================================================================== diff -u -r21ba197508c6498ea0c39f495526f4acd947df1e -r06de6d9d14714b1905646ae0b7ac2db629d1d72b --- vectorcast/Hercules_RM46_HD_Project/environment/VOLTAGES/VOLTAGES.tst (.../VOLTAGES.tst) (revision 21ba197508c6498ea0c39f495526f4acd947df1e) +++ vectorcast/Hercules_RM46_HD_Project/environment/VOLTAGES/VOLTAGES.tst (.../VOLTAGES.tst) (revision 06de6d9d14714b1905646ae0b7ac2db629d1d72b) @@ -292,6 +292,36 @@ TEST.EXPECTED:uut_prototype_stubs.isPersistentAlarmConditionCleared.isErrorOccurred:0 TEST.END +-- Test Case: checkVoltageRanges.010 +TEST.UNIT:Voltages +TEST.SUBPROGRAM:checkVoltageRanges +TEST.NEW +TEST.NAME:checkVoltageRanges.010 +TEST.NOTES: +This is an automatically generated test case. + Test Path 4 + (1) for (i < (NUM_OF_MONITORED_LINES)) ==> TRUE + (2) if (volts > MAX_VOLTAGES[i]) ==> TRUE + Row number 1 forms a pair with Row 2 for Condition #2, subcondition "a". + Condition a ==> TRUE + Test Case Generation Notes: + Cannot set i due to assignment + Conflict: Unable to control expression-to-expression comparison in branch 1 +TEST.END_NOTES: +TEST.STUB:Voltages.getMonitoredLineLevel +TEST.VALUE:Voltages.getMonitoredLineLevel.return:<> +TEST.VALUE:uut_prototype_stubs.activateAlarm2Data.alarm:ALARM_ID_HD_VOLTAGE_OUT_OF_RANGE +TEST.VALUE:uut_prototype_stubs.activateAlarm2Data.alarmData1.dataType:ALARM_DATA_TYPE_F32 +TEST.VALUE:uut_prototype_stubs.activateAlarm2Data.alarmData1.data.uInt.data:0 +TEST.VALUE:uut_prototype_stubs.activateAlarm2Data.alarmData2.dataType:ALARM_DATA_TYPE_F32 +TEST.VALUE:uut_prototype_stubs.activateAlarm2Data.alarmData2.data.uInt.data:2139095039 +TEST.VALUE:uut_prototype_stubs.isPersistentAlarmConditionCleared.return:1 +TEST.VALUE:uut_prototype_stubs.getDGOpMode.return:DG_MODE_INIT +TEST.EXPECTED:Voltages.getMonitoredLineLevel.signal:MONITORED_LINE_1_2V +TEST.EXPECTED:uut_prototype_stubs.isPersistentAlarmConditionCleared.alarmIndex:ALARM_ID_HD_AC_POWER_LOST +TEST.EXPECTED:uut_prototype_stubs.isPersistentAlarmConditionCleared.isErrorOccurred:0 +TEST.END + -- Test Case: checkVoltageRanges_ACPowerLoss TEST.UNIT:Voltages TEST.SUBPROGRAM:checkVoltageRanges