Clone Tools
  • last updated a few seconds ago
Constraints
Constraints: committers
 
Constraints: files
Constraints: dates
LEAHI-DD-FIRMWARE-LDT-3749_Ability to set operation sub mode on DD subsystem
LEAHI-DD-FIRMWARE-LDT-3749_Ability to set operation sub mode on DD subsystem
Balancing chamber switching control

Balancing chamber switching control

Can this statement be 'else if' case after BC switch only request handling (after line 1013). Just in case both requests (switch only and regular one) came together and only 'switch only' handled f...

Can this statement be 'else if' case after BC switch only request handling (after line 1013). Just in case both requests (switch only and regular one) came together and only 'switch only' handled first.

remove the space before false.

remove the space before false.

Remove blank line

Remove blank line

Remove blank line.

Remove blank line.

I tried the suggested change and tested. But it did not provide the expected results. If a on was requested while an off was still pending to be processed, the off-request flag gets cleared without...

I tried the suggested change and tested. But it did not provide the expected results.
If a on was requested while an off was still pending to be processed, the off-request flag gets cleared without the actual request being processed and the off request was never executed.

Not sure these min/max are right here either.

Not sure these min/max are right here either.

So we have all temp sensors getting averaged now, right? So should we have one get function that takes a sensor ID as param?

So we have all temp sensors getting averaged now, right? So should we have one get function that takes a sensor ID as param?

Remove extra blank lines.

Remove extra blank lines.

Remove this reference (across the file) if the implementation is updated.

Remove this reference (across the file) if the implementation is updated.

Update the deadband timing in the comments.

Update the deadband timing in the comments.

Remove blank line. Also, add comments on the key logics for reference.

Remove blank line. Also, add comments on the key logics for reference.

Default case rise count should be 2, instead of 1?

Default case rise count should be 2, instead of 1?

Now that we go with pressure slope detection logic, we don't want to use pressure-based detection for Low Qd. correct?

Now that we go with pressure slope detection logic, we don't want to use pressure-based detection for Low Qd. correct?

The BC valves not even opened and collecting the spent dial pressure as last previous spent dial pressure may not be correct.

The BC valves not even opened and collecting the spent dial pressure as last previous spent dial pressure may not be correct.

LDT-3522 heater control update

  1. … 1 more file in changeset.
Done.

Done.

Done

Done

Done.

Done.

LDT-3522 updating heater control

  1. … 5 more files in changeset.
Same comment.

Same comment.

Having much larger P coeff is likely to cause a lot of oscillations and very slow to get to stable target.